Brand Name : SKYLINE

Model Number : SL-7606Z

Certification : CE

Place of Origin : China

MOQ : 1 unit .

Price : negotiated

Payment Terms : T/T, L/C, Western Union, MoneyGram

Supply Ability : 1 unit/ month

Delivery Time : 10 work days

Packaging Details : plywood case

Test station : 1 station, one sample at a time

Test size : Length > 1200 mm

Combustion gas : propane with purity of 98%

Combustion supporting gas : compressed air. (air pressure needs to reach more than 10 Mpa)

Timer : 0 to 99.99 s/m/h arbitrary setting

Flame temperature : 450 to 950℃

Power supply : AC380 (±10%) V/50HZ

Power : 1KW

Trolley size : L450 * W910 * H540 mm

Sample bracket size : L1200 * W430 * H700 mm

Control chamber size : L1000 * W1000 * H1750 mm

Contact Now

IEC 60331 Cable Circuit Integrity Fire Resistance Tester

Application

The tester is designed according to GB/T 19216.11-2003/IEC 60331-11:1999 "Line integrity test of cables and optical cables under flame conditions Part 11: test apparatus - individual fire supply with flame temperature not lower than 750℃". It fully conforms to GB/T 19216.21-2003/IEC 60331-21:1999 "Line integrity test of cables and optical cables under flame conditions" Testing Procedures and Requirements Part 21: Test Procedures and Requirements - Cables rated at 0.6/1.0 kV and Below GB/T 19216.23-2003/IEC 60331-23:1999 "Line Integrity Test for Cables and Optical Cables under Flame Conditions Part 21: Test Procedures and Requirements - Data Cables" and GB/T19216.25-2003/IEC60331-25:1999 "Electricity under Flame Conditions. Test of line integrity of cable and optical cable twenty-first parts: test procedures and requirements -- optical cable " test standard. It is suitable for testing the integrity of the cable or optical cable when it is fired at no less than 750℃.

Standards

GB/T 19216.11-2003 / IEC 60331-11:1999, GB/T 19216.21-2003 / IEC 60331-21:1999, GB/T 19216.23-2003 / IEC 60331-23:1999, GB/T19216.25-2003 / IEC60331-25:1999

Main parameters

Test station

1 station, one sample at a time

Test size

Length > 1200 mm

Sample bracket

There are three bracket rings in the machine. In the test, the sample is placed on the bracket ring and fixed with two side fixtures. The inner diameter of the metal ring is about 150 mm

Stainless steel test carrier, bearing

30kg

Combustion gas

propane with purity of 98% (customer supplied)

Combustion supporting gas

compressed air. (air pressure needs to reach more than 10 Mpa)

Timer

0 to 99.99 s/m/h arbitrary setting

Flame temperature

450 to 950℃

Power supply

AC380 (±10%) V/50HZ

Power

1KW

Trolley size

L450 * W910 * H540 mm

Sample bracket size

L1200 * W430 * H700 mm

Control chamber size

L1000 * W1000 * H1750 mm


Product Tags:

IEC 60331 Fire Resistance Test Equipment

      

IEC 60331 Fire Resistance Test Machine

      

BS 6387 Fire Resistance Test Equipment

      
Cheap IEC 60331 Cable Circuit Integrity Fire Resistance Test Machine BS 6387 Cable Fire Resistance Test Equipment for sale

IEC 60331 Cable Circuit Integrity Fire Resistance Test Machine BS 6387 Cable Fire Resistance Test Equipment Images

Inquiry Cart 0
Send your message to this supplier
 
*From:
*To: SKYLINE INSTRUMENTS CO.,LTD
*Subject:
*Message:
Characters Remaining: (0/3000)